SS Instructions

 

SS Joining Clips with Gasket : Installation Instructions

Hang the SS joining clip with gasket over the PF flange installed at the end of the duct or fitting.

Place the flange of next duct section to be assembled into the lower half of the joining clip.

Tighten the M4 hexagonal socket head screw (Allen key).
Not suitable for frequent opening.

Max. Torque : 1,5 Nm

For SR joining clips made of stainless steel use a stainless steel lubricating anti-seize compound and tighten the nut slowly by hand.

For the SS joining clips without gasket:
Apply the self-adhesive gasket in the middle of the flange, otherwise the air-tightness class C (DIN EN 12237) might not be achieved.

It is recommended to install the Joining Clips equipped with a self-adhesive seal rather quickly (a few days), otherwise the seal may come off.